Installation
Notice
Improper installation can compromise the function of the BTL and result in damage.
Ensure that no strong electrical or magnetic fields are present in the direct vicinity of the BTL.
Be sure to maintain the specified distances and separations.
Note
For dimensions, see Product description.
Any orientation is permitted. Mount the BTL on a level surface of the machine using the provided mounting clamps and cylinder-head screws.
Clamp types and the required number of clamps depend on the sensor version and measuring length (see Mounting clamps).
Arrange the clamps at irregular intervals to help prevent resonance caused by vibration loads. Observe the recommended maximum distance between clamps (see Number and spacing of mounting clamps).
Insert the BTL into the mounting clamps.
Fasten the BTL to the machine using the mounting screws. Observe the maximum tightening torque for the clamp type (see Mounting clamps).
Install the magnet (accessory; see Accessories).
The profile-housing sensor can be used with both floating (non-contacting) magnets (see {ref}Floatingmagnet) and captive magnets (see {ref}captivemagnet).
### Electrical Connection
The electrical connection is made via a plug connection
(for pin assignment see {ref}`tab-s92-connector` or {ref}`tab-s01-connector`) .
```{note}
See the information about Shielding and cable routing {ref}`here <shielding-cable-routing>`.
Pin |
…-E11AA… |
…-E11A1… |
…-E11AE… |
…-E11A5… |
|---|---|---|---|---|
1 |
19,2…28,8 V |
|||
2 |
0…10 V |
10…0 V |
4…20 mA |
20…4 mA |
3 |
GND[1] |
|||
4 |
0V |
|||
5 |
Unassigned[2] |
|||
Pin |
…-E11AA… |
…-E11A1… |
…-E11AE… |
…-E11A5… |
|---|---|---|---|---|
1 |
GND / 0 V |
|||
2 |
0…10 V |
10…0 V |
4…20 mA |
20…4 mA |
3 |
19,2…28,8 V |
|||
4 |
FE (Functional Earth) |
|||
Shielding and cable routing
Note
Defined ground!
The BTL and the control cabinet must be at the same ground potential.
Shielding
Observe the following instructions to ensure electromagnetic compatibility (EMC):
A shielded cable between BTL and controller can be used to increase EMC in the application. Shielding: Braided copper shield with minimum 85% coverage.
Magnetic fields
The position measuring system is a magnetostrictive system. Ensure that there is sufficient distance between the BTL and the transducer/holding cylinder and strong, external magnetic fields.
Cable routing
All cables between BTL, control and power supply must be routed tension-free. To prevent electromagnetic interference, ensure sufficient distance from high-current cables and cables carrying high-frequency voltage signals (e.g. from frequency converters).
Note
Only approved cables with a minimum cross-sectional area of AWG 24 may be used. All connected cables must have a temperature resistance of at least 80 °C. Use copper conductor, only.
Cable length
The maximum cable length is 30 m.[3]