Process Data Profiles

The device supports only one process data profile. The process data mapping in this profile is described in the following two chapters.

For more details on process data profiles and settings see chapter Process Data Info and Configuration.

PDInput

Byte

Value

Byte 13

Supply monitor

Byte 12

Port error status

Byte 11

Analog value out of range status

Byte 10

Pin 1 short circuit status

Byte 8-9

Digitalized Input Value on Port 8

Byte 6-7

Digitalized Input Value on Port 7

Byte 4-5

Digitalized Input Value on Port 6

Byte 2-3

Digitalized Input Value on Port 5

Byte 1

Switch point 2

Byte 0

Switch Point 1

Switch point 1

Bit

Value

Bit 7

Switch Point 1 - Port 8

Bit 6

Switch Point 1 - Port 7

Bit 5

Switch Point 1 - Port 6

Bit 4

Switch Point 1 - Port 5

Bit 3

Reserved

Bit 2

Reserved

Bit 1

Reserved

Bit 0

Reserved

Switch point 2; Wire break information

Bit

Value

Bit 7

Switch Point 2 - Port 8

Bit 6

Switch Point 2 - Port 7

Bit 5

Switch Point 2 - Port 6

Bit 4

Switch Point 2 - Port 5

Bit 3

Reserved

Bit 2

Reserved

Bit 1

Reserved

Bit 0

Reserved

Pin 1 short circuit

Bit

Value

Bit 7

Pin 1 short circuit - Port 8

Bit 6

Pin 1 short circuit - Port 7

Bit 5

Pin 1 short circuit - Port 6

Bit 4

Pin 1 short circuit - Port 5

Bit 3

Pin 1 short circuit - Port 4

Bit 2

Pin 1 short circuit - Port 3

Bit 1

Pin 1 short circuit - Port 2

Bit 0

Pin 1 short circuit - Port 1

Pin 1 Analog value out of range status

Bit

Value

Bit 7

Analog value underflow - Port 8

Bit 6

Analog value underflow - Port 7

Bit 5

Analog value underflow - Port 6

Bit 4

Analog value underflow - Port 5

Bit 3

Analog value overflow - Port 8

Bit 2

Analog value overflow - Port 7

Bit 1

Analog value overflow - Port 6

Bit 0

Analog value overflow - Port 5

Pin 1 Port error status

Bit

Value

Bit 7

Error status - Port 8

Bit 6

Error status - Port 7

Bit 5

Error status - Port 6

Bit 4

Error status - Port 5

Bit 3

Error status - Port 4

Bit 2

Error status - Port 3

Bit 1

Error status - Port 2

Bit 0

Error status - Port 1

Supply monitor

Bit

Value

Bit 7

Reserved

Bit 6

Overvoltage UA

Bit 5

Reserved

Bit 4

Overvoltage US

Bit 3

No UA

Bit 2

Undervoltage UA

Bit 1

Reserved

Bit 0

Undervoltage US

PDOutput

Byte

Value

Byte 6-7

Analog output value on Port 4

Byte 4-5

Analog output value on Port 3

Byte 2-3

Analog output value on Port 2

Byte 0-1

Analog output value on Port 1